| General specifications |
|
|
| Signal type |
Analog input |
| Functional safety-related parameters |
|
|
| Safety Integrity Level (SIL) |
SIL 2 |
| Supply |
|
|
| Connection |
Power Rail or terminals 14+, 15- |
| Rated voltage |
20 … 35 V DC |
| Ripple |
within the supply tolerance |
| Power dissipation |
1.4 W |
| Power consumption |
1.8 W |
| Input |
|
|
| Connection side |
field side |
| Connection |
terminals 1+, 2-, 3 or 5-, 6+ |
| Input signal |
0/4 … 20 mA |
| Voltage drop |
≤ 2.4 V at 20 mA (terminals 5, 6) |
| Input resistance |
≤ 64 Ω terminals 2-, 3 ; ≤ 500 Ω terminals 1+, 3 (250 Ω load) |
| Available voltage |
≥ 16 V at 20 mA terminals 1+, 3 |
| Output |
|
|
| Connection side |
control side |
| Connection |
terminals 7-, 8+, 9 |
| Load |
0 … 800 Ω at 20 mA |
| Output signal |
0/4 … 20 mA (overload > 25 mA) |
| Ripple |
max. 50 µA rms |
Reviews
Clear filtersThere are no reviews yet.